Consider setting up all aspects of the control valve handwheel

Web Design And Seo For www.china-webdesign.com
solenoid valve suppliers – China Manufacturer
Thank you for inquiry my solenoid valve suppliers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valve-suppliers-3/

 
        Shall require the supplier to provide the basic error parameters of the valve dead zone parameter and distribution of electricity / gas valve positioner control valve control valve. A

As valve dead zone parameter should not be greater than 2%, the basic error of the distribution / gas valve positioner control valve should be less than ± 10%, with the digital valve

Door positioning device, the basic error of the control valve should be less than ± 1%.

        Should be noted that the control valve on the pressure of the gas source. Check the control valve actuator according to the actual situation of the device, instrument air pressure

Requirements. If the device in the instrument air pressure can not meet the requirements of the implementing agencies, the valve supplier shall replace the implementing agencies, should provide

High-quality instrument air should be at least meet the following requirements: Clean, dry, and does not contain corrosive impurities, gas containing solid particles

Less than 0.1g/m3 particle diameter of not greater than 3μm, an oil content not greater than 1 x 10 (-6 power), caused by the locator According to statistics, due to the gas source is not clean

Is not working properly accounted for more than 60% of the failure rate of the entire locator.
 
        The general design units have selected the body core (valve core, valve seats, valve stem, valve cage, ring, packing, gaskets)

Materials. Final valve selection should be consistent with the design requirements, and if not, must confirm that the material change is appropriate, if in doubt, you must

For technical clarifications.

       Control valve arrival, you should promptly notify the supplier out of the box, requires the supplier to send personnel to participate in commodity inspection, if the supplier is issued

Fax or letter to confirm and recognize the user\\ s out-of-the-box results. Inspection personnel should be detailed records of all the commodity inspection results should not miss any details, but

And the inspection results and the Contract Technical Annex to the control, a note of the deviation, and inspection reports with timely feedback to the supplier, and requirements in a timely manner at

Management. Try not to delay the time of inspection out of the box, otherwise it may affect the claims and progress of the project. Also to note is that the control valve No.

Body, executive body and the attachment model, serial number and other parameters should be recorded, to make the record work order with goods accessories for later use. Because

If you do not write down these parameters, the control valve after prolonged use, on the nameplate will be vague and difficult to recognize, there may be

Nameplate is lost, and some parameters required for purchase of spare parts.

      Order digital locator software required, just state the name of the software and annotated to provide delivery of the latest version can be software

The version number can not write.

      Spare parts and control valve with the order to save costs, the number of procurement of spare parts to 1 to 2 years to meet the needs of the normal production of the principle of

. If you do not know, the use of the control valve parts may require the supplier recommended, taking into account financial factors.

      Avoid bundling tender. Two or more different goods and control valve with the procurement, if a package of both cheap goods

Performance is poor or extremely expensive goods, are not allowed to unpacking, it is difficult to achieve co-existence of choice.

      Proposed payment and delivery schedule, product quality, services, linked to set aside a certain amount of retention money for the supplier to provide the product quality

And the assessment of quality of service.

      If unidirectional flow through the media of the control valve, control valves must not reverse the installation, otherwise it will affect the flow capacity of the valve, the flow of special

Sealing performance and operation stability.

      Signing of the contract, the contract in the Technical Annex, a product supplier supply is not working or fails

Supplier shall promptly provide products for debugging to deal with the problems, or replacement, and provide temporary substitutes, shall not in any

What reason to delay the deal with the problem affect the user\\ s normal production, or will be poor quality of service to pursue the responsibility of the supplier; Once the problem-solving, the

Costs incurred, should identify the reason for the two sides discuss their problems.
      Port into the line of control valve accessories should be bottom-up access, should not the reverse, to prevent water damage to parts. If the cable must be top-down

Access should be an appropriate extension cable, ensure that a U-shaped bend before entering the terminal mouth. So that rain water will not enter the secondary instrument. If you are using

Threading pipe, should be left in the U-shaped bend of the lower part of the outfall. When the cable leads from the instrument cable tray should be noted that the threading pipe on the bridge interface

The direction of the nozzle must not be up; and respond to the nozzle to be sealed to eliminate the possibility of water.

Posted in Uncategorized | Tagged , , | Comments Off

Control valve of choice

Web Design And Seo For www.china-webdesign.com
solenoid valves manufacturers – China Manufacturer
Thank you for inquiry my solenoid valves manufacturers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valves-manufacturers-73/

 Control valve type, material, and pipe connections, attachment options, the signing of the preparation of tender documents, evaluation, technical contracts, security

Installation, maintenance is a complex process of any one part of a loophole, are likely to affect the use of the control valve. Although there are a variety of books

Membership, standards and software for designers and users, technical staff and generally will not have much difficulty, but from the process design

Process parameters to control valve of the tender documents issued tenders, tender evaluation, technical clarification, the formation of the evaluation report, approve the bid evaluation reports, technical negotiations

Signed a technical contract to the out-of-the-box inspection, installation, commissioning and put into use, generally have to go through quite a long time, during a little the effect will be

Negligence or omissions of one or more may cause plant losses and affect the progress of the project. This article only a few times in Anhui Huainan Chemical Group Co., Ltd.

Procurement control valve and the process of using the experience and understanding a summary of the proposed procurement to control the valve should have sufficient time, as long as the technical conditions

Have to advance the preparation of tender documents, evaluation, technical clarifications, to sign a technical contract work, really careful and meticulous work to do deep, less

The technology flaws. As for the progress of the business contract, they should according to the progress of the project and funding decisions.

Posted in Uncategorized | Tagged , , | Comments Off

Dalian Henry ball valves and control valves exported to international markets

Web Design And Seo For www.china-webdesign.com
solenoid valves – China Manufacturer
Thank you for inquiry my solenoid valves, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/

The Dalian Henry monitoring and control instrumentation engineering the second batch of exports to Colombia Ball has been completion of the performance testing, waiting for the unpacked

.
   
    The products are used in crude oil and natural gas control on the technical requirements for products and product quality requirements are very high. In the company improve the quality management

Under the control of the system and strict inspection system, the product has reached a higher level of quality. This is Henry companies export to Colombia is also

The products, the first batch of products has been through the actual use of foreign praise. In addition, the control valve products had been successfully exported to Spain

India and other countries used in the process control system.

Posted in Uncategorized | Tagged , , | Comments Off

Development of control valves in the direction

Web Design And Seo For www.china-webdesign.com
solenoid valve manufacturer – China Manufacturer
Thank you for inquiry my solenoid valve manufacturer, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valve-manufacturers-5/

The development direction of the main control valve for the intelligent, standardized, refined, rotation, and enhancing safety.

(1) intelligence and standardized intelligence and standardization of the control valvehas been on the agenda. Intelligent smart positioner.

Intelligent technology in the following areas.

① self-diagnostic control valve, the operational status of telecommunications and other intelligent features, easy management of control valve, fault diagnosis easier, but also

Reduces the maintenance of the skills requirements.

② to reduce the product type, simplifying the production process. Smart valve positioner not only can easily change the control valve flow characteristics, can also be mentioned

High control quality control system. Therefore, to simplify and standardize the requirements of the control valve flow characteristics (for example, only the production of linear characteristics of control

Valve) o intelligent function module to match the characteristics of the controlled object, the control valve types and varieties greatly reduced, so that the control valve system

Making process is simplified, and in the production and market tested and recognized.

③ digital communications. Digital communication is widely available in the control valve to the HART communication protocol based on some of the control valve positioner

The input signal and valve position signal to achieve the same transmission line; Fieldbus technology based, control valves and valve positioner and PID control functions

Module and control functions at the field level, so that the risk of dispersion, to make the control more timely, more quickly.

④ smart valve positioner. The smart valve positioner has all the features of the valve positioner, to improve the dynamic and static control valve

Features to improve the control precision of the control valve, smart valve positioner in the coming period as a control valve auxiliary equipment

Widely used.

Posted in Uncategorized | Tagged , , | Comments Off

The Masoneilan LNG device control valves

DresserMasoneilan ? control valves have been selected for the Angola LNG Project. Contract by Bechtel\\ s oil and gas and chemical products global

Business units (Bechtel) to grant the company to undertake the engineering, procurement and construction of the offshore part of the project. Dreiser Masoneilan will provide

For the universal maintenance of control valves, including 21000 Series and 41005 Series reciprocating globe valve and 35002 series Camflex ? II rotary globe valve for

A variety of applications throughout the device. The first batch of valves are expected to start shipping in the summer of 2009. A waterfront in the northern Zaire province in Angola

Community-Soyo, near a single liquefied natural gas system will produce liquefied natural gas, liquefied petroleum gas, such as propane and butane, condensate, as well as home

Piped gas. It will have annual production capacity of 6.8 billion cubic meters. Construction earlier this year, expected to begin production in early 2012.

Posted in Uncategorized | Tagged , , | Comments Off

On the control valve procurement selection

Web Design And Seo For www.china-webdesign.com
pneumatic air cylinders – China Manufacturer
Thank you for inquiry my pneumatic air cylinders, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-pneumatic-air-cylinders-7/

Correct choice of end connections (connection of the annular surface / convex connection / right clip-on) in the form of control valves and process piping. With the flange, such as to require valve

Supplier between the valves and flanges, gaskets, and should indicate in the Technical Annex of the contract requirements and the flange material, pressure rating and flange to take over

The tube label. Clip-on control valve itself if a single flange, flange connection hole carrier silk thread should be metric, if the thread contained Bi inch should be

Requirements of the valve the supply side with the connecting bolts.

If the control valve with solenoid valve, it is recommended that the contract in the Technical Annex part of the technical parameters of solenoid valve to indicate the manufacturer, brand, voltage level, anti

Burst form, material requirements and the control valve on and off the travel time requirements, but do not need to specify the specific model of the solenoid valve model by valve

Supplier selection type, but according to the final calculation or factory test should indicate whether to allow the supplier to control gas solenoid valve as a pilot

Valve. When the control valve actuator requirements of the air volume in order to shorten the travel time of the control valve, the solenoid valve as a pilot valve and the flow capacity

Pneumatic Following the actuators used in combination, can reduce costs, but also increased the number of attachments, because the increase of the gas path links the increase means that the point of failure

Discuss technical attachment should be to determine whether to allow the gas control program.

Recommended regardless of the diaphragm actuator or piston actuator should be equipped with air filter pressure reducer, the executing agency driven gas source of

Pressure.

Prior to shipment, the control valve is equipped with accessories should be connected in the production plant complete and tested, in line with the requirements of the contract the Technical Annex. Control valve

Supply-side valve applications, the decision connecting pipe is steel pipe, PVC jacket tube or stainless steel pipe, valve travel time requirements

Decides that the gas line connection pipe diameter. General control valve of the gas line connection pipe diameter of not less than 8 × 1mm too small will cause the response of the control valve

Too slow, of course, if the control valve switch trip time permits, can also be used for 6 × 1mm diameter gas line connecting pipe.

Control valve diameter size should be consistent with the design documents, if you must change the engineer through the process piping, equipment and related professional should be

Reported (for example, does not allow changes to the relevant professionals should discuss with the decision to change the program) to make the appropriate design changes.

 Should pay attention to the problem of corrosion of the valve. If the procurement of the control valve cavitation, flashing, cavitation, erosion and other problems, you should pay attention to whether to take

Corresponding processing means, can avoid these problems or to minimize the possibility of occurrence of these phenomena. Valve body, valve, valve cage,

Ring material should be rigid steel or alloy steel, nitriding treatment or surface coating (such as plating Sri Lanka too Levin). Should absolutely avoid control

System valve cavitation in a variety of conditions.

 Must have the installation location of the attachment of the valve Dimensions and locators in the Technical Annex of the contract confirmation requirements to determine the control valve

The installation space, attachment mounting positions of the drawings if there are conflicts between the installation location of the available space. Such a conflict exists, we should first confirm whether the

Change the installation location and orientation of the mounting positions of the control valve actuator or valve attachments. If the position of the valve can not be changed, you should notice the process

, Pipes, equipment, electrical and other relevant professionals as soon as possible to modify the layout and the trend of design.

Contracting parties should be required material analysis reports provide key components of the control valve, control valve leakage test reports, pressure test, the test report, and form a test

Report or compliance certification, the gas line connection diagram, the control valve pressure test procedures, methods and test control valve leakage test procedures, methods,

For inspection and review.

 The RFP should require bidders to provide the selection of samples of the control valve (model-specific code in the sample, abbreviations should be explained in detail) should be

With performance. Technology contracts should require the contract to provide routine maintenance manual valve body and its annex, the annex to the dealer and vendor contact to

Address, fax, and telephone number.

 Control valve attachment level of protection should not be lower than IP54/NEMA4 (the level of protection of the digital valve positioner generally IP65/NEMA4X), wiring

Inlet and outlet ports of the box should be sealed.
Control valve applications bit in the valve plate reflected, or a separate note

In a sign and attached to the valve. In addition to double out on the body to visibly mark the valve to allow the media by the direction.

; Handwheel is set according to the control valve applications, and key considerations.

Shall require the supplier to provide the basic error parameters of the valve dead zone parameter and distribution of electricity / gas valve positioner control valve control valve. General, the valve

The dead zone parameter should not exceed 2%, the basic error of the distribution / gas valve positioner control valve should be less than ± 10%, if equipped with a digital positioner

The basic error of the control valve should be less than ± 1%.

Should be noted that the control valve on the pressure of the gas source. According to the actual situation of the device, check the control valve actuator instrument air pressure. As

Instrument air pressure in the fruit unit can not meet the requirements of the implementing agencies, the valve supplier should replace the executing agency should provide high-quality

Instrument air should be at least meet the following requirements: clean, dry, and does not contain corrosive impurities, the gas containing solid particles of less than

0.1g/m3, the particle diameter of not more than 3μm, an oil content not greater than 1 x 10 (-6 power) caused by the locator According to statistics, due to the gas source is not clean can not be

Normal work conditions accounted for more than 60% of the entire locator failure rate.

; The general designer of the design units have been selected core body parts (spool, valve seats, valve stem, valve cage, ring, packing, gasket) material.

Final valve selection should be consistent with the design requirements, and if not, must confirm that the material change is appropriate, if in doubt, you must be a technical

Technical clarification.

Control valve arrival, you should promptly notify the supplier out of the box time to require the supplier to send personnel to participate in commodity inspection, if the supplier by fax or to

Letter of confirmation, and endorsed the results of the user out of the box. Inspection should record the results of all the commodity inspection, you should not miss any details, but should the provider

Review the results and contract technical annex to the control, a note of the deviation, together with inspection reports and timely feedback to the supplier, and requirements in a timely manner for processing. Feel

We can not delay the time of inspection out of the box, otherwise it may affect the claims and progress of the project. Another to note is that the bit number control valve, the valve body, the Executive

Line agencies and accessories, model, serial number and other parameters should be recorded, to make the record work order with goods accessories for later use. If you do not

Timely note of these parameters, the control valve after prolonged use, on the nameplate will be vague and difficult to recognize, there may be lost nameplate

Loss, and some parameters required for purchase of spare parts.

The latest version you can order digital locator software required, just state the name of the software and annotated to provide delivery, software version number

Can not write.

Spare parts and control valve with the order, the cost savings, the number of procurement of spare parts to meet the needs of the normal production of the principle of 1 to 2 years. If

Usage of the control valve components is not clear, may require the supplier recommended, taking into account financial factors.

Avoid bundling tender. Purchasing two or more different goods and control valves, both in a package of cheap goods and performance

Poor or extremely expensive goods, are not allowed to unpacking, it is difficult to achieve co-existence of choice.

Proposed payment and delivery schedule, product quality, services, linked to set aside a certain amount of retention money for the supplier to provide the product quality and service

Quality assessment.

If unidirectional flow through the media of the control valve, control valves must not reverse the installation, otherwise it will affect the flow capacity of the valve flow characteristics, density

Sealing performance and operation stability.

Signing of the contract, the contract in the Technical Annex, a supplier suppliers supply products can not be the normal use or failure

Should be promptly provided for debugging to deal with the problem of the existence of, or replacement, and provide temporary substitutes for any reason

Delay in processing affect the user\\ s normal production, or will be poor quality of service to pursue the responsibility of the supplier; once the problem is, the occurrence of

Costs, should identify the reason for the two sides discuss their problems.
 Port into the line of control valve accessories should be bottom-up access, should not the reverse, to prevent water damage to parts. If the cable must be a top-down access

Should be appropriate to lengthen the cables, to ensure that a U-shaped bend before entering the terminal port. So that rain water will not enter the secondary instrument. If you use threading

Tube should be left in the U-shaped bend of the lower part of the outfall. Threading pipe in the direction of the interface on the bridge should be noted that when the cable leads from the instrument cable tray

The nozzle must not be up; and respond to the nozzle to be sealed to eliminate the possibility of water. Control valve type, material, and pipe connections

Access way, the choice of attachment, the preparation of tender documents, evaluation, technical contracts signed, installation, maintenance is a complicated process, any

A part of a loophole that may affect the use of control valves. Although there are a variety of books, standards and software for designers and users

Technical personnel for reference, generally do not have too much difficulty, but from the process design of process parameters in preparation for the control valve of tender documents

Issued tenders, tender evaluation, technical clarifications, formation evaluation report, the approval of the bid evaluation reports, technical negotiations, signed a technology contract, to unpacking inspection, installation

, Debug, and put into use, generally have to go through quite a long time, during a little to the effect would be negligence or missed one or several, may work

Plant losses and affect the progress of the project. This several times purchasing some of the control valve and use in Anhui Huainan Chemical Group Co., Ltd.

And understanding of a summary, the proposed procurement of control valves should be sufficient time, as long as the technical conditions are met, to advance the preparation of tender documents

, Evaluation, technical clarifications, signed a technical contract work, really careful and meticulous work to do deep, less technical flaws. As for the progress of the business contract,

Will have to decide according to the progress of the project and funding.

Posted in Uncategorized | Tagged , , | Comments Off

Supply valves check valves control valve

Web Design And Seo For www.china-webdesign.com
solenoid valves manufacturers – China Manufacturer
Thank you for inquiry my solenoid valves manufacturers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valves-manufacturers-73/

Ai Johnson (Aixun,) is a global leader in the pipeline systems of industrial MRO distributors, we uphold the years specialized in piping systems services and business

Business philosophy, by virtue of the place of MRO products, excellent quality, adequate cash reserves, and rapid logistics network for Chinese enterprises to provide professional

One-stop service of the pipeline systems of industrial MRO procurement, to help the normal operation of their facilities, and to enable them to save procurement time and reduce their

Procurement costs.
    Ai Johnson (Aixun,) is the joint formed by the shareholders of many enterprises. And set up on Haiyi Johnson Industries, Ai Jackson industrial equipment, Ai Jackson valves Ai

Johnson fittings, Ai Jackson network, the corporate sector, with their own brand of 8, 18 close companies, more than 160 partners.
    Ai Johnson (Aixun,) MRO production or agent of the distribution of products has more than 100,000 varieties of 11 categories, all products according to Chinese standards, the International

Standards of production, sales, and some of the products has been made in the European Community CE, American UL, CCS, the U.S. ABS, Lloyd s LR, UK, Norway, DNV international certification, the whole

Ministry of the enterprise through the ISO2000 international quality certification, and some 14001 environmental certification. The products are widely used in petroleum, chemical, steel, steam

Vehicles, electric power, shipbuilding, mining and other fields, enterprises preferred piping system one-stop supplier of industrial MRO procurement.
    

Posted in Uncategorized | Tagged , , | Comments Off

Service and customer value

Web Design And Seo For www.china-webdesign.com
solenoid valve manufacturers – China Manufacturer
Thank you for inquiry my solenoid valve manufacturers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valve-manufacturers-5/

    Aixun the MRO, the full range of products: pumps, valves, fittings, tubing, piping instrumentation, pipe tools, pipe accessories, 11

Line, more than 100,000 domestic and foreign brands of industrial products to ensure that the maximum extent to meet the customer s product selection needs
    
    2, with the Ai Johnson (Aixun,) the MRO sufficient inventory to minimize customer inventory investment through centralized procurement of large quantities, enabling customers to total

Body of procurement costs and save customers time and effort
    
    3, the product of professional and efficient consulting, convenient product ordering, fast stop full service logistics customer procurement manpower resources

Has been optimized
    
    4, the international ISO quality system certification, a comprehensive after-sales service system. Guarantee the cut-off and loss of working time caused by the customers due to inferior products
    
    , Ai Johnson (Aixun,) has been focusing on services, care about every detail, our employees can fully understand customer needs and do everything we serve

, Ai Johnson (Aixun,) the spirit of enthusiasm, rigorous, pragmatic, up "the belief warmly welcome new and old customers at home and abroad, the presence of partners and

Guidance.

Posted in Uncategorized | Tagged , , | Comments Off

Flowserve Corporation to improve the control valve safety and reliability

Web Design And Seo For www.china-webdesign.com
solenoid valve suppliers – China Manufacturer
Thank you for inquiry my solenoid valve suppliers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valve-suppliers-3/

Industrial areas of flow, including the global infrastructure markets, including oil and gas, power generation, chemical, water, paper, mining, and general industry

Body control products and services, a leading provider of Flowserve Corporation, through improved design to further improve the the Fox Valtek MaxFlo eccentric rotation

The safety performance of the control valve.
 
Fox Valtek MaxFlo 3 "valve upgrade" American Society of Mechanical Engineers (ASME) standards, to provide rugged valve

Axis "out of the anti-protection, to prevent the stem in the case of pressure loss or pop. Meet the specifications of ASME B 16.34 in Section 6.5.1 "

An important safety features, has become the the Valtek MaxFlocontrol valve of standard design. "Sudden incidents, security incidents, as well as a variety of failure

Are often caused by the lack of such safety features of the valve, "Fox production manager, Christophe Granger," we have

The improved design will enable it to operate under the harshest conditions. "
 
"The Valtek MaxFlo 3" flange spacing of two kinds of sizes to choose from, that is, eccentric rotary valve standard size of the ISA-75.08.02, as well as direct

Control valve ISA-75.08.01 or DIN 3202 the F1. The new straight-through valve size selection allows users under the conditions allow, in straight

Easily through the valve and eccentric rotary valve conversion. To retain the original MaxFlo industry-leading design performance, "MaxFlo 3" partial

Heart cock control valve features a non-through shaft design, in order to achieve higher Cv values ??in a given valve size, and corrosive medium on stem

The damage is reduced to the minimum. Other important features include bi-directional tight shutoff, low opening torque.
 
"All of these features ensure the MaxFlo 3 precise controllability and reliability, Mr. Granger, said," High performance is MaxFlo 3 control

Valve core design principles of the most important one. "

Posted in Uncategorized | Tagged , , | Comments Off

The development of the control valve in the direction of intelligent

Web Design And Seo For www.china-webdesign.com
solenoid valves manufacturers – China Manufacturer
Thank you for inquiry my solenoid valves manufacturers, Tel:0086-574-88869817, Email:jelpc@jelpc.com
http://www.jelpc.com/key-solenoid-valves-manufacturers-73/

Intelligence and standardization of the control valve has been on the agenda, intelligent smart valve positioner, intelligent performance in the following areas.

    (1) self-diagnostic control valve operational status of telecommunications and other smart features that make the control valve to facilitate management, fault diagnosis easier

, But also lowers the maintenance of the skills requirements.

    (2) reduce the product type, simplifying the production process. Smart valve positioner not only can easily change the control valve flow characteristics can also be

Improve the control system to control quality. Therefore, to simplify and standardize the requirements of the control valve flow characteristics (for example, only the production line characteristics of the control valve

). Intelligent function module and charged with object properties match the types and varieties of the control valve products to greatly reduce, control valve system

Making process has been simplified. In order to reduce the variety of control valves, also domestic manufacturers to produce full-function control valve, these intelligent methods will continue to increase

And in the production and market tested and recognized.

    (3) digital communications. Digital communication is widely available in the control valve, based on the HART communication protocol, some of the control valve valve

Locator input signal and valve position signal to achieve the same transmission line; Fieldbus technology based, control valves and valve positioner, the PID control

System function module combines control functions at the field level, the risk of dispersion control more timely, more quickly.

    (4) intelligent valve controller. The smart valve positioner has all the features of the valve positioner to improve the dynamic of the control valve and

Static characteristics, improve the control precision of the control valve, so the smart valve positioner period of time in the future become an important control valve auxiliary set

Prepared to be widely used